Wind upgrade eval: the sensor said it failed
A wind farm in Scotland upgraded one turbine and left its neighbors alone for most of a year. I used the farm's open operating data to check whether the upgrade paid off, and found that the turbine's own wind sensor reported the gain as a loss.
A Gridledger module built on real operating data. Data from the Hill of Towie wind farm open dataset, released by RES on behalf of TRIG under CC BY 4.0.
The story in three parts
The upgrade added about 3%
T13 produced 2.9% more energy against its four nearest turbines once season and wind direction were matched. The publisher's own analysis puts it at 4.3%.
A routine check would have called it a fault
After the upgrade, T13's wind sensor read 9.7% higher than its neighbors'. Against its own sensor, the turbine looked weaker at every wind speed.
Small gains stay invisible
Turbines with no upgrade drifted 1.2% against their neighbors. A gain under about 3% on one turbine sits inside that noise, and a 2024 software trial worth 1.1% didn't reproduce.
What the numbers say
energy gain for the upgraded turbine, corrected for season and wind direction
shift in that turbine's own wind reading after the upgrade, against its neighbors
drift of turbines with no upgrade at all, the noise any single-turbine check has to beat
The question
An owner pays for a retrofit on a turbine. A year later, can they tell from their own data whether it worked?
The owner's data should be able to answer that, but a turbine's output swings with the weather far more than any upgrade moves it. Gridledger's premise is that operating data from many vendors can sit in one place and answer questions like this one. This module tests that premise on real data, and tests how far the answer can be trusted.
A natural experiment, in the open
One turbine got an aerodynamic upgrade in September 2021. Its neighbors got the same upgrade, but not until mid 2022.
The Hill of Towie wind farm has 21 turbines of 2.3 MW each. RES released ten years of its SCADA data on behalf of the owner, TRIG: ten-minute records of power, wind and turbine state, an alarm log, and a separate log of downtime that combines SCADA with the operator's own records. The release documents each upgrade and its dates, and RES's analysis code is public.
T13's upgrade work ran from 23 to 29 September 2021. Work on the next turbine didn't start until 14 July 2022, so T13 ran upgraded beside unchanged neighbors for nine months. The test compares T13 with T09, T11, T12 and T14, its four nearest turbines. RES's analysis uses the same four.
How an upgrade check could mislead an owner
Each failure mode below has a check, and the check's result.
| Failure mode | The check | What it found |
|---|---|---|
| The turbine's own sensor reads a gain as a loss | Compare power against the neighbors' wind as well as the turbine's own | T13's sensor read 9.7% higher against its neighbors after the upgrade, so its own power curve showed a drop at every wind speed |
| Season or wind direction passes for a gain | Match the before period to the same months a year earlier, and compare within wind direction and speed bands | The corrected estimate moved from 3.2% to 2.9%, with a narrower range |
| Normal drift passes for a gain | Run the same method on turbines with no upgrade and a fake date | They averaged +0.2%, drifted 1.2% (one standard deviation) and peaked at 2.5%; T13 is above all of them |
| The range looks surer than it is | Check how often the placebo ranges contain zero | 11 of 16 did, where a correct 90% range would hold zero about 14 or 15 times, so the ranges run too narrow |
| A fault hides inside the comparison | Use only ten-minute intervals where every compared turbine ran, and check the operator's downtime log | T06 was shut down for about eight months; the four placebo runs it disrupted are left out of the summary |
T13 produced more than its neighbors after the upgrade
Corrected for season and wind direction, the gain is 2.9%, with a range of 1.6% to 4.3%.
The simplest version divides T13's energy by its neighbors' average, month by month, using only intervals when all five turbines ran. T13 out-produces them even before the upgrade, most likely because of where it stands in the layout, so the step matters more than the level.
The corrected version compares the after period with the same months a year earlier, so winter is set against winter, and compares the turbines within each 30 degree wind direction band and 1 m/s wind speed band. Wind direction comes from the neighbors' nacelle positions, corrected to true north with the values RES publishes.
| Test | Simple method | Corrected | Publisher |
|---|---|---|---|
| One turbine, 2021 | 3.2% (0.4% to 5.5%) | 2.9% (1.6% to 4.3%) | 4.3% (3.3% to 5.3%) |
| Nine turbines, 2024 | 0.9% (-3.8% to 6.3%) | 2.6% (0.1% to 5.1%) | 1.1% (0.2% to 2.0%) |
Why a standard power curve would have flagged a fault
The upgrade shifted T13's own wind reading by +9.7% against its neighbors, enough to turn a gain into an apparent loss.
The usual health check plots a turbine's power against the wind speed its own nacelle sensor reports. The sensor sits behind the rotor, so a change to the blades can change what it reads. Against its own sensor, T13 after the upgrade looks weaker at every wind speed. Against the wind its neighbors measured, it's stronger.
How big a gain can this kind of check see?
On turbines that had no upgrade, the same method found "gains" of up to 2.5%.
To measure the method's noise, I ran it on every other turbine with a fake upgrade date and its own four nearest neighbors. Nothing changed on any of them, so every result should be zero. Four runs were left out because T06's long outage removed most of their after data. The other 16 averaged +0.2%, so the method isn't biased, but they drifted 1.2% (one standard deviation) and reached 2.5% at most.
T13's 2.9% is larger than every placebo result, so the upgrade shows clearly. A gain under about 3% on a single turbine would not. The test also showed that the method's own ranges run too narrow: only 11 of the 16 placebo ranges contained zero, where a correct 90% range would hold zero about 14 or 15 times.
A smaller upgrade the method couldn't confirm
In 2024 the farm trialed a software upgrade on nine turbines. RES measured 1.1%. This method can't confirm it.
The simple version lands at 0.9%, near RES's figure, but its range runs from -3.8% to 6.3%. The corrected version gives 2.6%. Several turbines were still getting the earlier upgrade in spring 2023, so the season-matched before period shrinks to summer only. RES's method adds long-term wind weighting and other corrections this page leaves out.
The choice of neighbors matters as much as the method. RES puts T08 in two test groups; against one set of neighbors it gains +1.0%, against the other -1.6%. That spread is larger than the effect being measured.
The other half of lost production
T06 was shut down from late September 2021 to May 2022, about eight months.
An upgrade raises output while a turbine runs; downtime is the energy lost while it doesn't. The operator's log, from January 2021 to mid July 2022, puts T06 at 47.2% of the period, against a fleet median of 3.5%. The log covers the whole outage, including a month the SCADA feed missed. T20 and T15 each had a single outage lasting weeks. The dataset doesn't say what failed, so the cause stays unnamed here.
| Turbine | Time shut down | Hours |
|---|---|---|
| T06 | 47.2% | 6,335 |
| T20 | 15.9% | 2,132 |
| T15 | 10.8% | 1,455 |
| T18 | 6.3% | 845 |
| Fleet median | 3.5% |
A separate measure built from the turbines' own run-time records, the share of time each was stopped while most of the farm ran, ranks the same four turbines worst.
How it was built
A Python script reads the yearly SCADA archives in place and writes small result files; this page is generated from those files.
The script reads the zipped monthly tables without unpacking them and keeps the few columns it needs. Each download was checked against the checksum Zenodo publishes. Test groups, exclusion periods and the compass corrections come from RES's public analysis code. The turbine make and model are left out on purpose.
Claude, an Anthropic model, wrote and ran the analysis code in a working session with me, proposed the placebo test and drafted this page. I chose the dataset and the question, approved each download, called T06's outage a separate fault before the operator log confirmed it, and decided what the page claims.
Where it doesn't hold
- It isn't the publisher's method. It leaves out long-term wind weighting, detrending and reanalysis wind data, which is why the 2024 trial didn't reproduce.
- The ranges run too narrow. The placebo test showed it, so read each range as the least the uncertainty could be.
- One farm, one turbine model. The 1.2% noise level belongs to this site and this layout.
- Wind direction comes from nacelle positions. Ten-minute averages of an angle can be wrong near north, and the compass corrections are RES's, not checked here.
- The sensor finding is one turbine. The +9.7% shift is measured; airflow changed by the upgrade is the likely cause, but it wasn't tested.
- It measures energy, not money. There's no revenue or payback figure here.
Data: Clerc, A., and Lingkan, E. (2026). Hill of Towie wind farm open dataset, version 2.1.0. Zenodo. doi.org/10.5281/zenodo.22662930 ↗. Released by RES on behalf of TRIG under CC BY 4.0 ↗. Test groups, exclusions and compass corrections from RES's hill-of-towie-open-source-analysis ↗ (BSD 3-Clause, copyright 2024 Renewable Energy Systems Limited). Figures on this page are my analysis, not the publisher's, except where marked.